DC inverter modular chiller Hisense Hi-Mode VE1 Series 65 kW

Hi-Mod VE1 series chillers adopt full DC inverter technology and feature EVI technology, which facilitates strong heating at low ambient temperature and greatly improves energy efficiency.

Categories: , SKU: HFRWVE-65DPF/AE
12 219.88 € VAT included
DC inverter modular chiller Hisense Hi-Mode VE1 Series 65 kW цена - Chillers | BGR Group
Buy withtbi bank logo
13 x €1041.17
12 ВНОСКИ
1140.52 евро
Кредитен калкулатор UNI Credit 1.4.0
Само няколко клика до желаната покупка от 75 евро до 25 000 евро:

1. Добавете желания от Вас продукт в кошницата.

2. В меню "Метод на плащане" изберете "На кредит с УниКредит Кънсюмър Файненсинг".

3. Изберете брой месечни вноски, според Вашите възможности и предпочитания.

4. Завършете кандидатстването изцяло дигитално или очаквайте телефонно обаждане.

Цена на артикула
12219.88 евро
Брой месеци за погасяване *
Размер на погасителна вноска
. евро
ГЛП
%
ГПР
%
* Срокът на изплащане се заявява при приключване на поръчката.
Откажи
Добавете в количката

Inverter EVI compressor for highly efficient heating

A new generation DC inverter scroll compressor is used, which contributes to sustainable heating at low outside temperature by significantly improving power and energy efficiency. All Hi-Mod VE1 series products use inverter technology, meaning all scroll compressors are of the high efficiency DC EVI type and all fans are DC inverter motors, thus providing exceptional benefits to the user.

EVI compressor with secondary compression with minimal power loss at low outside temperature

Thanks to the EVI technology with secondary compression and economizer, the high-efficiency EVI compressor can significantly improve the heating or cooling performance and in particular optimize the heating circuit, which is able to significantly increase its heat output, realizing higher performance at low outdoor temperature .

  • Thanks to the EVI technology, the operating range of the system is wider compared to that of a conventional installation. The lower limit of the range can reach -26ºC.
  • The supply water temperature can reach up to 55ºC, covering the conditions for heating with radiators.
  • The supply water temperature can reach up to 55ºC at an external temperature of -5ºC and, respectively, up to 45ºC at an external temperature of -25ºC.

  • Compared to a conventional constant speed chiller, the relative cooling energy efficiency is increased by 20%.

Smooth fan speed control

The Hi-Mod VE1 series use a variable speed DC fan motor that greatly reduces electrical consumption. The speed is smoothly adjusted according to the outside temperature and the required cooling load, just like the inverter technology used in the compressor, resulting in reliability and high energy efficiency.

  • Ensuring stable pressure at the inlet and outlet of the compressor.
  • Freon movement is easier, and the dedicated power of the indoor unit is guaranteed.
  • Accurate and fast coverage of current energy demand with changing load.

Oil management

  • Equipped with a high-efficiency external oil separator, the oil separation efficiency is as high as 98%, which significantly reduces the circulating oil in the system (below 2%) and improves the energy efficiency of the chiller.
  • The compressor has a built-in oil filter to ensure the cleanliness and quality of the oil during its life cycle.
  • The compressor has a built-in hydraulic pump that actively supplies oil at all times, at any speed mode, ensuring trouble-free lubrication.

Intelligent energy regulation technology

  • In constant speed units, power control consists of how many of the compressors are on or off. Supply water temperature varies dramatically and compressors run at full load at low output.
  • In the modules with inverter control, the control of the output power is carried out by frequency regulation of the operation of the compressor. In the case of a combination of modules, each system can automatically adjust the frequency control. In this way, the temperature of the supplied water varies within small limits, and the productivity factor increases by 15-20%.

Technical parameters

ModelHFRWVE-65SPF/AEHFRWVE-130DPF/AE
Maximum cooling power kW63126
Maximum heating power kW68136
Power consumed during coolingkW22.143.4
Consumed heating power kW 22.4 44.6
Maximum power consumption kW 26,5 53
Current consumption when cooling А 36 72
Current consumption during heating A 3774
Maximum current consumption A 48 96
COP/EER -2.85/3.042.9/3.05
SEER -4.714.61
SCOP (T submission 45°C) -2.872.91
Power management - inverter
Power supply - AC 3φ, 380~415V/50Hz
Water flow m3/h 10.8 21.7
Water resistance (without filter) kPa 35 35
Water resistance (with filter) kPa 45 45
Pipe diameter (return/feed) - G2-1/2" external thread
Maximum pressure to water heat exchanger Mpa1
Control type - Automatic by microcomputer
Compressor type - DC inverter spiral
Number of compressors No. 12
Fan Type - Axial DC inverter
Flow rate m3/h 24400 43000
Number of items p 2 2
Freon Type - R410a
Loaded kg 15.52×14.0
Dimensions WxHxD mm 765×1725x1950 1100×2360x2190
Dimensions with packaging WxHxD mm 840×1860x2030 1160×2485x2250
Weight Net weight kg 490 910
Gross weight kg 520 940
in operational mode kg 510 930
Sound power dB(A) 81 84
Operating range Cooling °C -15~48
Heating °C -26~43
T of water supply Cooling °C 5~15
Heating °C 35~55