Water-cooled chillers CLINT CWW/IY/WP 1352 ÷ 4402
Water cooled chiller from 386 kW to 1439 kW
are loaded with the R410A environmental refrigerant and are designed to meet the needs of small and medium-sized domestic and industrial systems that require medium and low power, compact size and quiet operation. These chillers are designed for year-round household production, autonomous heating in winter and cooling in the summer. Very economical chiller with a high degree of reliability. Flexibility is the main advantage of these chillers.
| Power (Model): | 220 – 2500 kW (Maxi Power) |
|---|---|
| Type: | Water – Water |
Water cooled chillers
of the CWW / IY / WP 1352 ÷ 4402 series with R134a refrigerant are designed to meet the needs of large enterprises in the service and production sectors. The aggregates of the series are equipped with screw compressors with inverter technology, furnace heat exchangers and are available in a super silent version. The optimization of water and cooling circuits and the inverter screw compressor enable aggregates to achieve high efficiency and reduced power consumption with proper sizing of the installation and proper application.
Water-cooled chillers CLINT CWW/IY/WP, main futures:
- Structure with galvanized sheet frame with polyester powder coating;
- Inverter screw compressor with built-in oil separator, suction side filter, oil level visor, built-in thermal protection in the compressor, car heater and hot gas safety valve;
- Cowhide evaporator with easy to remove cast iron bottom for easy access and maintenance. Each refrigeration circuit is equipped with a separate capacitor. Water connections for water tower and dry cooler; water connections for drilling as an option;
- Cavity tube evaporator with one or two independent refrigerators (depending on the model) and one water circuit;
- Electronic TRV;
- Freon R134a;
- The electrical panel includes: main switch with automatic door locking, fuses, overload protection of compressors;
- Microprocessor and control system;
Technical data
| CWW/IY/WP | 1352 | 1402 | 1602 | 1802 | 1952 | 2302 | 2702 | 3302 | 4402 | ||
| Heating | Heating capacity (1) | kW | 386 | 454 | 525 | 588 | 697 | 824 | 1033 | 1240 | 1439 |
| Energy consumed (1) | kW | 82 | 96 | 112 | 126 | 147 | 173 | 218 | 260 | 298 | |
| COP (1) | 4.71 | 4.73 | 4.69 | 4.67 | 4.74 | 4.76 | 4.74 | 4.77 | 4.83 | ||
| Heating (EN14511) | Heating capacity (1) | kW | 351 | 408 | 478 | 535 | 635 | 750 | 935 | 1121 | 1293 |
| Energy consumed (1) | kW | 81 | 97 | 112 | 124 | 146 | 172 | 220 | 268 | 305 | |
| COP (1) | 4.34 | 4.22 | 4.29 | 4.31 | 4.34 | 4.36 | 4.25 | 4.19 | 4.24 | ||
| Cooling | Cooling power (2) | kW | 319 | 375 | 433 | 490 | 576 | 686 | 848 | 1007 | 1171 |
| Energy consumed (2) | kW | 65 | 76 | 88 | 100 | 117 | 137 | 173 | 205 | 237 | |
| EER (2) | 4.91 | 4.93 | 4.92 | 4.90 | 4.92 | 5.01 | 4.90 | 4.91 | 4.94 | ||
| Cooling (EN14511) | Cooling power (2) | kW | 318 | 374 | 431 | 489 | 574 | 684 | 845 | 1003 | 1167 |
| Energy consumed (2) | kW | 68 | 79 | 92 | 104 | 122 | 143 | 180 | 215 | 248 | |
| EER (2) | 4.71 | 4.71 | 4.67 | 4.71 | 4.71 | 4.78 | 4.69 | 4.66 | 4.71 | ||
| Compressor | Number | n° | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 |
| Refrigeration circuit | n° | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | |
| Steps | n° | Straightforward | |||||||||
| Evaporator | Water flow | l/s | 15.24 | 17.92 | 20.69 | 23.41 | 27.52 | 32.78 | 40.52 | 48.11 | 55.95 |
| Loss of pressure | kPa | 33 | 40 | 47 | 35 | 43 | 44 | 45 | 56 | 51 | |
| Pipe connection | DN | 125 | 150 | 150 | 150 | 200 | 200 | 200 | 200 | 200 | |
| Capacitor | Water flow | l/s | 18.35 | 21.55 | 24.89 | 28.19 | 33.11 | 39.32 | 48.78 | 57.91 | 67.27 |
| Loss of pressure | kPa | 49 | 58 | 68 | 51 | 61 | 63 | 66 | 81 | 73 | |
| Pipe connection | DN | 125 | 150 | 150 | 150 | 200 | 200 | 200 | 200 | 200 | |
| Electrical characteristics | Power supply | V/Ph/Hz | 400/3/50 | ||||||||
| Max. Operating current | A | 201 | 231 | 256 | 284 | 330 | 390 | 485 | 572 | 649 | |
| Max. Starting current | A | 87 | 95 | 107 | 109 | 140 | 153 | 201 | 243 | 293 | |
| Sound power | STD (2) | dB(A) | 69 | 70 | 70 | 70 | 70 | 70 | 72 | 73 | 75 |
| SSL (2) | dB(A) | 64 | 65 | 65 | 65 | 65 | 65 | 67 | 68 | 70 | |
| Weight | Transport weight | kg | 2550 | 2940 | 3010 | 3400 | 4090 | 4500 | 5060 | 5650 | 6300 |
| Operating weight | kg | 2810 | 3470 | 3510 | 3860 | 4800 | 5250 | 5810 | 6620 | 7450 | |
Remarks:
- Cold water from 12°C to 7°C and condenser temperature from 30°C to 35°C;
- Sound level measured at 1 m from the location of the unit according to ISO 3744;
- N.B. The weight of the SSL version is specified in the technical documentation
Dimensions
| CWW/IY/WP | 1352 | 1402 | 1602 | 1802 | 1952 | 2302 | 2702 | 3302 | 4402 | ||
| L | STD | mm | 4000 | 4300 | 4300 | 4300 | 4300 | 4300 | 4300 | 4600 | 4600 |
| P | STD | mm | 1200 | 1400 | 1400 | 1400 | 1500 | 1600 | 2200 | 2200 | 2200 |
| H | STD | mm | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 |
![]() |
CWW/IY/WP 1352 ÷ 4402 | ||
| A | mm | 500 | |
| B | mm | 500 | |
| C | mm | 500 | |
| D | mm | 800 | |
Documents